Level measurement
98
Continuous level measurement in liquids
4. Instrument selection within the measuring principle
Installation instructions hydrostatics (differential pressure)
Closed tanks with FMD78 (capillary diaphragm seal)
• Level measurement is only safeguarded between the upper edge of the lower and the lower edge of the upper diaphragm seal • In vacuum applications, it is recommended to install the pressure transmitter below the lower diaphragm seal. This will avoid a vacuum load of the diaphragm seal caused by the presence of filling oil in the capillaries
max.
p 2
min.
p 1
C
Endress+Hauser Applicator Further installation instructions are presented in the "Sizing Diaphragm Seal" Applicator