Proline t-mass F_I 300_500

Technical data

7

Cross section – t-mass F (left), t-mass I (right)

Sensor with long-term stability and bidirectional measurement Metallic seal Flow conditioner

Messaufnehmer Nennweiten Sensor Nominal diameter

• Einpfad-Ausführung: DN 25 (1") • Zweipfad-Ausführung: DN 50…300 (2…12") • t-mass F: DN 15 to 100 (½ to 4") • t-mass I: DN 80 to 1500 (3 to 60") • t-mass F: flanges (EN, ASME, JIS), threads (EN 10226-1/ISO 7-1, ASME MNPT) • t-mass I: compression fittings G / NPT (¾", 1") t-mass F: 0.38 to 2900 Nm 3 /h (0.23 to 1800 sft 3 /min) t-mass I: 1613 to 567 236 Nm 3 /h (1020 to 358 474 sft 3 /min) max. PN 40 (Class 300) –40 to +180 °C (–40 to +356 °F) Standard: IP66/67 (Type 4X enclosure) Option (Proline 500): IP68 (Type 6P enclosure) bis 50 m/s (164 ft/s) 2…100 bar (29…1450 psi) –50…+150 °C (–58…+302 °F) IP66/67 (Type 4X enclosure)

Prozessanschlüsse Flansche: EN, ASME Min./Max. Durchfluss 0,5…9426 m3/h (17,7…332 890 ft3/h) Process connections

Max. Durchfluss- geschwindigkeit Min./max. flow (air)

Prozessdruck

Prozesstemperatur Process pressure Process temperature Degree of protection Max. measured error (mass flow) Repeatability Schutzart Max. Messabweichung Messdynamik Werkstoffe

Volumenfluss: Standard: ±1,0% v.M. bei 3…40 m/s (9,84…131,2 ft/s) Option: ±0,5% v.M. bei 3…40 m/s (9,84…131,2 ft/s) • Messaufnehmergehäuse: Aluminium, rostfreier Stahl Druckguss • Messrohr: rostfreier Stahl 1.4408/1.4409 (CF3M) ±1.0% o.r. (10 to 100% o.f.s.) ±0.1% o.f.s. (1 to 10% o.f.s.) ±0.25% o.r. Up to 1000:1 1.4404/1.4435 (316L), Alloy C22 Negligible – ATEX, IECEx, cCSAus, EAC, NEPSI, INMETRO – PED, CRN – NACE MR0175/MR0103 Über 133:1 Kein Druckverlust • ATEX, IECEx, CCSAUS • SIL • PED, CRN

Temperatur: ±0,35 °C ± (0,002 · T) °C (±0,63 °F ± 0,0011 · [T – 32] °F) Druck: ±0,5% v.M. Schallgeschwindigkeit: ±0,2% v.M. • Prozessanschlüsse, Temperatursensor, Drucksensor: rostfreier Stahl 1.4404 (316, 316L) • Ultraschallwandler: rostfreier Stahl 1.4404 (316, 316L), Titan Grade 2

Druckverlust Zulassungen Turndown Materials (wetted parts) Pressure loss Approvals Conformity

• NACE MR0175/MR0103 • Funkzulassung • OIML R137, AGA 9

The t-mass F/I 300/500 measuring system fulfills the EMC requirements according to IEC/EN 61326 and NAMUR NE21. It also conforms to the requirements of the EU and ACMA directives and thus carries the and the mark.