Level measurement
18 Continuous level measurement in liquids
3. Selection of the measuring principle according to the application
Non-contact
B
Our proposal Radar Micropilot
Ultrasonics Prosonic
(separated)
(compact)
FMU90
FDU9x
FMU4x
FMR5x
FMR6xB
Advantages
• Non-contact and unaffected by head pressures
•High resistance • Self-cleaning effect of sensors • Integrated alarm/point level relay • Fast measuring frequency (4-wire)
• Universally useable due to •Flexible measuring range • Changing, highly viscous or •Remote access via Bluetooth® • Heartbeat Technology
aggressive media (100% PTFE)
Technical data • Connection •Accuracy • Process temperature • Process pressure • Process connection
2-/4-wire (HART®, DP) ±2mm/±0.08", +0.2% of the distance –40 to +105°C/–40 to +221°F +0.7 to +4bar/+10 to +58psi Threads, Tri-Clamp, flanges (DIN, ANSI, JIS)
2-wire (HART®, PA, FF, Ethernet-APL) ±1mm/±0.04" –196 to +450°C/–321 to +842°F –1 to +160bar/–14.5 to +2,320psi Threads, flanges (DIN, ANSI, JIS), hygienic connections 80m/262ft
25m/82ft
•Maximum
measuring range
Application limits
•Strong formation of foam •Many obstacles in the radar beam
guided radar, hydrostatics guided radar, capacitance, hydrostatics hydrostatics
•Strong formation of foam •Vapor pressure
guided radar, hydrostatics radar, guided radar, capacitance
•Many obstacles
guided radar, capacitance, hydrostatics
• Low DC value
Please note: Radar continued on Page 34
Please note: Ultrasonics continued on Page 74
Made with FlippingBook Digital Proposal Maker