Level measurement
72
Continuous level measurement in liquids
4. Instrument selection within the measuring principle
Installation instructions guided radar – free field
Weather protection cover • Always recommended for outside installation to avoid strong temperature changes of electronics
Installation • Not in the center • Not above the fillstream • Any wall distance, avoid wall contact Nozzle • 150mm/6" are to be preferred • extension must be used
Measuring range • Smallest measuring range: 300mm/12" • Largest measuring range: 45m/148ft (longer upon request) • • Measurement is possible up to the blocking distance (BD), on principle
C
Tank installations • Distance to obstacles min. 300mm/12" • During commissioning interference echoes can be suppressed
Turbulent surface/foam • Turbulent surfaces do not affect measurement
• Foam layers of up to approx. 100mm/4" do not affect measurement. Higher foam thickness may result in too small readings (depending on DC value)
Blocking distance (BD) and minimal distance from the tank bottom • Blocking distance top*: - Coax probe: 0mm/0"
•
* The blocking distance (BD) is preset from the factory. Depending from the application these settings can be adjusted.
tensioning weight area (0 to 250mm/10" from the end of the probe - lower blocking distance). Less accurate measurement is possible in the lower area of the probe.