Level measurement

Instrument selection within the measuring principle

73

Installation instructions guided radar – stilling well/bypass

Weather protection cover • Always recommended for outside installation to avoid strong temperature changes of electronics

Measuring range • Smallest measuring range: 300mm/12" • Largest measuring range: 10m/33ft (longer upon request)

Pipe diameter • diameters do not have any top blocking distance, measurement is possible up to the bottom edge of the process connection

Bypass/measuring tube • Metallic pipe • No special requirements of bypass pipe or stilling well • Welding seams protruding internally up to approx. 5mm/0.2" do not impair measurement • Wall contact by rod probes must be excluded. Use a centering disk at the end of the probe, if required Additional instructions for interface measurement • Rod probes can be installed up to a diameter of 100mm/4". For larger diameters, a coax probe is recommended • The pipe must not have any gradation • In case of interface layer measurement, the centering disk must be of plastic material